Power System Analysis Lecture Notes Ppt -

Generator: 10 MVA, 11 kV, ( X_d'' = 0.12 ) pu. Transformer 10 MVA, 11/132 kV, ( X_t = 0.08 ) pu. Line impedance 20 Ω (on 132 kV). Fault at 132 kV bus. Find ( I_f ) in kA.

Convert a 10% transformer reactance from 20 MVA, 132 kV to 100 MVA, 132 kV → ( Z_pu,new = 0.1 \times (1)^2 \times (100/20) = 0.5 ) pu. 3. Transmission Line Parameters (PPT Module 3) Resistance: ( R = \rho \fraclA ) (corrected for skin effect at 50/60 Hz). power system analysis lecture notes ppt

| Fault type | Connection at fault point | |------------|---------------------------| | Single line-to-ground (SLG) | Z1, Z2, Z0 in series | | Line-to-line (L-L) | Z1, Z2 in parallel | | Double line-to-ground (DLG) | Z1 in series with (Z2∥Z0) | Generator: 10 MVA, 11 kV, ( X_d'' = 0

[ Z_pu,new = Z_pu,old \times \left( \fracV_base,oldV_base,new \right)^2 \times \left( \fracS_base,newS_base,old \right) ] Fault at 132 kV bus

Zero-sequence current cannot flow if transformer delta or ungrounded wye on source side. 7. Power System Stability (PPT Module 7) Definition: Ability to return to synchronous operation after a disturbance.

neglected for overhead lines.